← Projects/P-08
Heat pump vs gas boiler: EES model and cost of heat
A group energy-systems practical in my master's at ICAI: we modeled a 25 kW air-to-water heat pump running on R290 (propane) in EES, ran it away from its design point, and compared it with a gas boiler on the cost of each megawatt-hour of heat and on CO2.
- 3.5
- COP at the design point, falling to 1.4 at −10 °C
- 64 vs 115
- €/MWh of heat: heat pump vs gas boiler (climate zone C)
- 2.9 – 3.9 yr
- payback, depending on the climate zone
- 69 – 75 %
- less CO2 than the boiler
01The model
The heat pump serves underfloor heating, warming water from 35 to 45 °C. We built the whole cycle in EES around a reciprocating compressor described by its physics: 70 % isentropic efficiency, a polytropic index of 1.154, 5 % clearance volume and 1,480 rpm nominal speed (2,220 rpm maximum), which sizes it at 455.3 cm³ per revolution. The condenser is checked on its T–Q diagram with a pinch-point loop, and the full EES code for design and off-design operation is in the report's annex.
02Off-design performance
At the design point the COP is 3.5. As the outdoor air gets colder the compressor has to work harder for the same heat, and at −10 °C the COP drops to 1.4. The model also gives the compressor speed and electrical input needed to follow the heat demand.
03Economics
We ran a full heating year for two Spanish climate zones. Zone C needs 58,186 kWh of heat and zone E 90,595 kWh; the heat pump covers them with 15,058 and 26,578 kWh of electricity, where a boiler would burn 71,763 and 111,734 kWh of gas.
- Levelized cost of heat: 64.0 / 67.5 €/MWh for the heat pump against 114.6 / 112.5 €/MWh for the boiler (zones C / E).
- Payback of the extra investment: 3.85 years in zone C and 2.89 years in zone E.
- CO2 savings: 75.2 % and 68.8 %.