Pick-and-place cell: control specification
A group project for the Industrial Automation course that sets out the control requirements for a cell in a toy factory. A gripper moves figurine bodies from a supply conveyor to a deposit conveyor, where assembly continues. The proposal covers six actuators, eight fault sources, batch counters, manual and automatic modes, and fault and emergency stops that only the operator can clear.
- 6
- actuators, 4 of them two-way and limit-switched
- 4 + 4
- fault sources: time-outs and contradictory limit-switch states
- 100 / 50 / 25
- batch sizes
- 3
- empty supply slots in a row trigger supply shortage
01The specification
The course supplied a template of ten requirements (P1–P10), several with a minimum number of actuators, timers, counters or parameters. Our group described the cell and wrote its proposal against them. This is the requirements stage. It defines what the controller must do and is not a program.
In automatic mode the gripper closes on a figurine body on the supply conveyor, lifts, turns, advances, lowers, releases the body onto the deposit conveyor and returns home. A pressure sensor on the deposit conveyor confirms each part, and that conveyor does not advance until it does.
- Actuators: four two-way axes (grip, lift, rotation, advance/retract), each limited by sensors, plus two one-way conveyors.
- Faults: four time-outs (part not picked from supply, part not reaching the deposit conveyor, deposit slot not freed, periodic maintenance due) and four contradictory input states, where both limit switches of one axis read active at once.
- Counters: batch sizes of 100, 50 and 25, and a count of consecutive empty supply slots. An empty slot makes the supply belt move on to the next position. Three empty slots in a row put the cell in supply-shortage mode.
- Modes: automatic runs until the batch is complete, then pauses. Manual mode is for testing. It runs one gripper cycle per button press, and each conveyor has its own button and moves only while that button is held.
- Emergency stop and re-arm: the mushroom button or a motor over-temperature sensor stops the cell. To leave fault or emergency mode, the controller needs a rising edge on a re-arm button that only the operator can press, so automatic operation never restarts without the operator.